By continuing use this site, you agree to the Terms & Conditions and our use of cookies.
      Fluke 1555 10 kV Insulation Tester
      • Fluke 1555 10 kV Insulation Tester
      • Fluke 1555 10 kV Insulation Tester

      Fluke 1555 10 kV Insulation Tester

      Fluke
      Reviews(1)

      Key features

      • Quickly configure, start and stop tests on the 1555 remotely, a safe distance away from any operating, energized equipment, using Fluke Connect® and a smart phone

      • Real time trending gives you easy-to-see visual cues, rather than hard to read, rapidly changing values

      • Report creation using Fluke Connect desktop saves time and makes test results easier to understand

      Quantity :
      testtesttest
      Allowed extensions: .pdf, .png, .jpeg, .gif, .jpg,
      • Secured
      • Fast Delivery
      • 7 days Return

      Key features

      • Quickly configure, start and stop tests on the 1555 remotely, a safe distance away from any operating, energized equipment, using Fluke Connect® and a smart phone

      • Real time trending gives you easy-to-see visual cues, rather than hard to read, rapidly changing values

      • Report creation using Fluke Connect desktop saves time and makes test results easier to understand

      • Fluke Connect saves test results to the cloud for analysis and preventive maintenance

      Product overview: Fluke 1555 FC 10 kV Insulation Tester Kit

      Evaluate the trends, eliminate the doubt

      The Fluke 1555 insulation resistance tester kit offers digital insulation testing up to 10 kV in an industrial strength case, with all the heavy duty leads and clips you need. Plus, the Fluke Connect wireless app performs tests and collects data while you stay a safe distance away.

      Remote operation lets you spend as little time as possible in potentially hazardous zones. Real-time trending shows a live graph on your phone, rather than a hard-to-read set of changing values. And you can create reports quickly, using pre-designed templates that you can customize with company logos.

      Reduce the risk, improve your results when conducting high-voltage insulation tests

      The world leading Fluke 1550C and 1555 insulation testers minimize the time you spend around powered equipment, while collecting data with one button push.

      Fluke insulation resistance testers now have Fluke Connect capability so you can:

      • Work from a safe distance, using the Fluke Connect wireless app to set parameters, perform tests and collect data on your smart phone

      • Select Ramp, PI, DAR and basic insulation tests

      • CAT III 1000 V, CAT IV 600 V safety rated

      • See trending graphs in real-time, create reports, with Fluke Connect app

      Fluke insulation testers can now conduct the entire range of test voltages specified in IEEE 43-2000 with a best in class, 3 year warranty and CAT IV 600 V safety rating.

      Other useful features:

      • Automatic calculation of Dielectric Absorption (DAR) and Polarization Index (PI) with no additional setup

      • Guard system eliminates the effect of surface leakage current on high-resistance measurements

      • Selectable test voltages in 50 V steps from 250 V to 1000 V, and 100 V steps above 1000 V

      • CAT III 1000 V, CAT IV 600 V safety rating

      • Warning function alerts the user that line voltage is present and gives the voltage reading up to 600 V AC or DC for increased user safety

      • Measurements can be stored in up to 99 memory locations, with each location assigned a unique, user defined, label for easy recall

      • Long battery life gives the user over 750 tests between charges

      • Large digital/analog LCD for easy viewing

      • Capacitance and leakage current measurement

      • Ramp function for breakdown testing

      • Resistance measurements up to 2 TΩ

      • Timer settings up to 99 minutes for timed tests

      • 3-year warranty

      Specifications: Fluke 1555 FC 10 kV Insulation Tester Kit

      Electrical Specifications

      The tester's accuracy is specified for one year after calibration at operating temperatures of 0°C to 35°C. For operating temperatures outside the range (-20°C to 0°C and 35°C to 50°C), add ±.25% per °C, except on the 20% bands add ±1% per °C.

      Insulation Resistance Measurement

      Test voltage (DC)

      250 V

      Range

      < 250 kΩ,

      250 kΩ to 5 GΩ

      5 GΩ to 50 GΩ

      > 50 GΩ

      Accuracy (± reading)

      Unspecified

      5%

      20%

      Unspecified

      500 V

      Range

      < 500 kΩ

      500 kΩ to 10 GΩ

      10 GΩ to 100 GΩ

      > 100 GΩ

      Accuracy (± reading)

      Unspecified

      5%

      20%

      Unspecified

      1000 V

      Range

      < 1 MΩ

      1 MΩ to 20 GΩ

      20 GΩ to 200 GΩ

      > 200 GΩ

      Accuracy (± reading)

      Unspecified

      5%

      20%

      Unspecified

      2500 V

      Range

      < 2.5 MΩ

      2.5 MΩ to 50 GΩ

      50 GΩ to 500 GΩ

      > 500 GΩ

      Accuracy (± reading)

      Unspecified

      5%

      20%

      Unspecified

      5000 V

      Range

      < 5 MΩ

      5 MΩ to 100 GΩ

      100 GΩ to 1 TΩ

      > 1 TΩ

      Accuracy (± reading)

      Unspecified

      5%

      20%

      Unspecified

      10000 V

      Range

      < 10 MΩ

      10 MΩ to 200 GΩ

      200 GΩ to 2 TΩ

      > 2 TΩ

      Accuracy (± reading)

      Unspecified

      5%

      20%

      Unspecified

      Bar graph range

      0 to 1 TΩ (1550C) - 0 to 2 TΩ (1555)

      Insulation test voltage accuracy

      -0%, +10% at 1 mA load current

      Induced AC mains current rejection

      2 mA maximum

      Charging rate for capacitive load

      5 seconds per μF

      Discharge rate for capacitive load

      1.5 s/μF

      Leakage current measurement

      Range

      1 nA to 2 mA

      Accuracy

      ±(5% + 2 nA)

      Capacitance measurement

      Range

      0.01 μF to 15.00 μF

      Accuracy

      ±(15% rdg + 0.03 μF)

      Timer

      Range

      0 to 99 minutes

      Resolution setting

      1 minute

      Resolution indication

      1 second

      Live circuit warning

      Warning range

      30 V to 660 V AC/DC, 50/60 Hz

      Voltage accuracy

      ±(15% + 2 V)

      Software specifications

      FlukeView Forms™ basic software requires a PC running Windows XP, Windows Vista , Windows 7 or Windows 8.

      General Specifications

      Display

      75 x 105 mm

      Power

      12 V lead-acid rechargeable battery, Yuasa NP2.8-12

      Charger Input (AC)

      85 V to 250 V AC 50/60 Hz 20 VA

      This Class II (double insulated) instrument is supplied with a Class 1 (grounded) power cord. The protective earth terminal (ground pin) is not connected internally. The extra pin is for added plug retention only.

      Dimensions

      269 x 277 x 160 mm (10.6 x 10.9 x 6.3 in)

      Weight

      3.7 kg (8.2 lb)

      Temperature (operating)

      -20°C to 50°C (-4°F to 122°F)

      Temperature (storage)

      -20°C to 65°C (-4°F to 149°F)

      Humidity

      80% to 31°C decreasing linearly to 50% at 50°C

      Altitude

      2000 m

      Enclosure sealing

      IP40

      Input overload protection

      1000 V AC

      Electromagnetic compatibility

      EN 61326

      Safety compliance

      IEC 61010-1: Overvoltage category II, Pollution Degree 2.

      IEC 61010-2-030: Measurement 600V CAT IV / 1000V CAT III

      IEC 61557-1, IEC 61557-2

      Fluke

      Specific References

      New product
      Andrew U07/01/2020
      Best product Ever

      I sincerely recommend this company industries Safety Nigeria for any industrial and marine Equipment for personal and company needs, its the best in-terms of quality and reliable products.

        Write your review
        Fluke 1555 10 kV Insulation Tester
        Fluke 1555 10 kV Insulation Tester

        Fluke 1555 10 kV Insulation Tester

        Allowed extensions: .pdf, .png, .jpeg, .gif, .jpg,