an industrial safety & marine products distribution company
an industrial safety & marine products distribution company
Specifications |
||
Maximum voltage between any terminal and earth ground |
600 V |
|
Surge protection |
6 kV peak per IEC 61010–1 600 VCAT III, Pollution Degree 2 |
|
Fuse for A input |
11 A, 1000 V FAST Fuse (Fluke PN 803293) |
|
Display |
Digital: 6,000 counts, updates 4 per second |
|
Bar graph |
33 segments, updates 32 per second |
|
Operating temperature |
-10°C to +50°C |
|
Storage temperature |
-40°C to +60°C |
|
Battery type |
9 volt Alkaline, NEDA 1604A / IEC 6LR61 |
|
Battery life |
400 hours typical, without backlight |
|
Accuracy Specifications |
||
DC millivolts |
Range/resolution |
600.0 mV / 0.1 mV |
Accuracy |
±([% of reading] + [counts]): 0.5% + 2 |
|
DC volts |
Range/resolution |
6.000 V / 0.001 V60.00 V / 0.01 V600.00 V / 0.1 V |
Accuracy |
±([% of reading] + [counts]): 0.5% + 2 |
|
Auto volts |
Range/resolution |
600.0 V / 0.1 V |
Accuracy |
2.0% + 3 (DC, 45 Hz to 500 Hz)4.0% + 3 (500 Hz to 1 kHz) |
|
AC millivolts¹ True RMS |
Range/resolution |
600.0 mV / 0.1 mV |
Accuracy |
1.0% + 3 (DC, 45 Hz to 500 Hz)2.0% + 3 (500 Hz to 1 kHz) |
|
AC volts¹ True RMS |
Range/resolution |
6.000 V / 0.001 V60.00 V / 0.01 V600.0 V / 0.1 V |
Accuracy |
1.0% + 3 (DC, 45 Hz to 500 Hz)2.0% + 3 (500 Hz to 1 kHz) |
|
Continuity |
Range/resolution |
600 Ω / 1 Ω |
Accuracy |
Beeper on < 20 Ω, off > 250 Ω detects opens or shorts of500 μs or longer. |
|
Ohms |
Range/resolution |
600.0 Ω / 0.1 Ω6.000 kΩ / 0.001 kΩ60.00 kΩ / 0.01 kΩ600.0 kΩ / 0.1 kΩ6.000 MΩ / 0.001 MΩ |
Accuracy |
0.9% + 1 |
|
Range/resolution |
40.00 MΩ / 0.01 MΩ |
|
Accuracy |
5% + 2 |
|
Diode test |
Range/resolution |
2.00 V / 0.001 V |
Accuracy |
0.9% + 2 |
|
Capacitance |
Range/resolution |
1000 nF / 1 nF10.00 μF / 0.01 μF100.0 μF / 0.1 μF9999 μF / 1 μF100 μF to 1000 μF |
Accuracy |
1.9% + 2 |
|
Range/resolution |
> 1000 μF |
|
Accuracy |
5% + 20% |
|
Lo-Z capacitance |
Range |
1 nF to 500 μF |
Accuracy |
10% + 2 typical |
|
AC amps True RMS (45 Hz to 500 Hz) |
Range/resolution |
6.000 A / 0.001 A10.00 A / 0.01 A |
Accuracy |
1.5% + 320 A continuous overload for 30 seconds max |
|
DC amps |
Range/resolution |
6.000 A / 0.001 A 10.00 A / 0.01 A |
Accuracy |
1.0% + 320 A continuous overload for 30 seconds max |
|
Hz (V or A input)² |
Range/resolution |
99.99 Hz / 0.01 Hz999.99 Hz / 0.1 Hz9.999 Hz / 0.001 Hz50.00 Hz / 0.01 Hz |
Accuracy |
0.1% + 2 |
|
1. All AC voltage ranges except Auto-V/LoZ are specified from 1% to 100% of range. Auto-V/LoZ is specified from 0.0 V.2. Temperature uncertainty (accuracy) does not include the error of the thermocouple probe.2. Frequency is AC coupled, 5 Hz to 50 kHz for AC voltage. Frequency is DC coupled, 45 Hz to 5 kHz for AC current.2. Temperature Range/Resolution: -40°F to 752°F / 0.2°F. |
||
Mechanical and General Specifications |
||
Size |
167 x 84 x 46 mm (6.57 x 3.31 x 1.82 in) |
|
Weight |
550 g |
|
Warranty |
3 years |