By continuing use this site, you agree to the Terms & Conditions and our use of cookies.
  • New
    Biocide Cooling Water
    • Biocide Cooling Water

    Biocide Cooling Water

    Review (0)

    The 7330 Cooling Water Biocide is a broad-spectrum, non-oxidizing biocide formulated to control microbial growth in closed-loop cooling systems. Microbial activity can lead to the formation of acids and biofilms, causing corrosion and reduced heat transfer efficiency. This biocide effectively mitigates such issues, ensuring optimal system performance.

    Quantity :
    testtesttest
    Allowed extensions: .pdf, .png, .jpeg, .gif, .jpg,
    • Secured
    • Fast Delivery
    • 7 days Return

     Key Features & Benefits

    • Broad-Spectrum Efficacy: Targets a wide range of microorganisms, including bacteria and fungi.

    • Non-Oxidizing Formulation: Safe for use with nitrite-based corrosion inhibitors, preventing potential chemical reactions.

    • Enhanced System Protection: Reduces the risk of underdeposit corrosion and maintains heat transfer efficiency.

    • Easy Application: Liquid form allows for straightforward dosing and integration into existing systems.

    Technical Specifications

    PropertyValue
    Appearance Clear, colorless to light green-yellow
    Density 1.03 g/ml
    pH 2.0 – 5.0
    Solubility Fully soluble in water
    Form Liquid

     Application Guidelines

    • Initial Dosage: Add 0.1 litre per ton of system capacity.

    • Heavily Fouled Systems: Increase dosage to between 0.2 and 0.9 litres per ton.

    • Application Method: Introduce the biocide into the system and circulate for 3 days.

    • Post-Treatment: After circulation, drain the system completely and flush with fresh water.

    • Refilling: Replenish with distilled water and add the appropriate corrosion inhibitor.

    • Re-testing: Conduct bacterial testing after 24 hours of operation to ensure effectiveness.

     Safety & Handling

    • Precautions: Avoid contact with skin and eyes.

    • Storage: Keep in a cool, dry place away from incompatible materials.

    • Usage Note: Do not use the system for producing potable water during the disinfection process.

    Specific References

    New product

    No customer reviews for the moment.

    Write your review
    Biocide Cooling Water

    20 other products in the same category:

    Biocide Cooling Water

    Biocide Cooling Water

    Allowed extensions: .pdf, .png, .jpeg, .gif, .jpg,