an industrial safety & marine products distribution company
an industrial safety & marine products distribution company
E7110-8A eight-channel analog input module measures and converts analog signals from common RTDs, thermocouples or 4-20 mA transmitters to digital data.
The module has an RS485 interface, supports industry-standard Modbus RTU / ASCII protocols as Modbus Slave unit and can be used in a variety of automation systems at Fieldbus level together with PLCs, HMIs or SCADA systems.
- 8 universal analog input channels
- Common RTD, TC, mV, mA inputs
- Standard input signals 0-1 V, 0/4-20 mA
- RS485 Modbus RTU /ASCII interface
Power supply: 90...264 VAC 20...375 VDC
Power consumption: ≤ 6 V·A
Number of inputs: 8
Supported transducers: thermocouples
RTD
dry contact relay or switch
U, I or R output devices
actuator position sensors
Digital filtering: independent for each input
Communication interface: RS485
Baud rate: up to 115 200 bit/s
Communication protocols: Modbus RTU,
Modbus ASCII
Dimensions: 63×110×73 mm
Weight: <0,5 kg
Mounting: to DIN rail or wall
Operating environment: safe indoor areas
Protection class: IP20
Operating conditions: -10...+55 °C, < 80 %RH, without condensation
E7110-8A eight-channel analog input module measures and converts analog signals from common RTDs, thermocouples or 4-20 mA transmitters to digital data. The device can be used in a variety of automation systems at the Fieldbus level together with PLCs, HMIs or SCADA systems. The Module operates in the RS485 network using Modbus RTU / ASCII protocols selected automatically. A device is a Slave unit, so the Fieldbus network must include a Master unit, e.g. a PC with running SCADA system, controller or regulator. The device is delivered with configuration software. PC with RS485/USB adapter (e.g. Evikon E1087) is used to configure the device. The product complies with the 2004/108/EC and 2014/30/EU Directives on electromagnetic compatibility.
Safety requirements
Always adhere to the safety provisions applicable in the country of use. The voltage of terminal contacts of the device is life-threatening. Only trained personal can operate the module.
Operating conditions
Non-ATEX-rated indoor spaces without aggressive gases, at atmospheric pressure (86...106,7 kPa), -10...+55 °С and 0...80% RH without condensation.
Installation and connection
The module is mounted to the wall or 35 mm DIN-rail and should be installed in the cabinet providing protection from moisture, dust and unauthorized access.
customer support