Specifications | ||
Voltage DC | Maximum voltage | 1000 V |
Accuracy | ±(0.09% + 2) | |
Maximum resolution | 0.001 V | |
Voltage AC | Maximum voltage | 1000 V |
Accuracy | ±(2% + 3) | |
AC bandwidth | 5 kHz1 | |
1. with low pass filter; 3 db @ 800 Hz | ||
Maximum resolution | 0.1 mV | |
Current DC | Maximum amps | 400 mA |
Amps accuracy | ±(0.2% + 2) | |
Maximum resolution | 0.01 mA | |
Current AC | Maximum amps | 400 mA |
Amps accuracy | ±(1.5% + 2)2 | |
2. 1 kHz bandwidth | ||
Maximum resolution | 0.01 mA | |
Resistance | Maximum resistance | 50 MΩ |
Accuracy | ±(0.9% + 2) | |
Maximum resolution | 0.1 Ω | |
Capacitance | Maximum capacitance | 9,999 µF |
Accuracy | ±(1.2% + 2) | |
Maximum resolution | 1 nF | |
Frequency | Maximum frequency | 100 kHz |
Accuracy | ±(0.1% + 1) | |
Maximum resolution | 0.01 Hz | |
Temperature Measurement | -40.0°C to 537°C | |
-40.0°F to 998°F excluding probe | ||
Diode test | Range/Resolution | 6 V / 1 mV |
Accuracy | ±(2% + 1) | |
Insulation Test | ||
Minimum test current @ 1kΩ/V | 1 mA | |
Test Voltages | 50, 100, 250, 500, 1000 V | |
Maximum resistance per test voltage | 50 V | |
100 V | ||
250 V | ||
500 V | ||
1000 V | 2 GΩ | |
Maximum resolution per test voltage | 50 V | 0.01 MΩ |
100 V | 0.01 MΩ | |
250 V | 0.1 MΩ | |
500 V | 0.1 MΩ | |
1000 V | 0.1 MΩ | |
Accuracy per test voltage | 50 V | ±(3% + 5) |
100 V | ±(3% + 5) | |
250 V | ±(1.5% + 5) | |
500 V | ±(1.5% + 5) | |
1000 V | ±(1.5% + 5) to 600 MΩ, ±(10% + 3) above 600 MΩ | |
Environmental Specifications | ||
Operating temperature | –20°C to +55°C | |
Storage temperature | -40°C to +60°C | |
Humidity (without condensation) | 0% - 95% (10°C – 30°C)0% - 75% (30°C – 40°C)0% - 40% (40°C – 55°C) | |
Operating altitude | 2000 m | |
Safety Specifications | ||
Overvoltage category | Complies with ANSI/ISA 82.02.01 (61010-1) 2004, CAN/CSA-C22.2 NO. 61010-1-04, and IEC/EN 61010-1 2nd Edition for measurement CAT III 1000 V and CAT IV 600 V | |
Agency approvals | 2000 m CAT III 1000 V, CAT IV 600 V; 3000 m CAT II 1000 V, CAT III 600 V | |
Mechanical and General Specifications | ||
Size | 203 x 100 x 50 mm (with holster) | |
Weight | 624 g | |
Warranty | 3 years | |
Battery life alkaline | Meter use | 1000 hours |
Insulation test u6se | Meter can perform at least 1000 insulation tests with fresh alkaline batteries at room temperature. These are standard tests of 1000 V into 1 MΩ with a duty cycle of 5 seconds on and 25 seconds off. | |
IP rating | IP40 |